Server Technology switched pro2 User Manual - page 164
Switched PRO2 – User Guide
Using the Command Line Interface (CLI)
•
164
Parameters
The set loadshed command uses the following parameters:
branch
Sets to allow branch shedding events.
line
Sets to allow line shedding events.
sensor
Sets to allows sensor shedding events.
ups
Sets to allow UPS shedding events.
Sub-Parameters
The set loadshed command uses the following sub-parameters:
all
Sheds outlets only when all UP devices on an upstream line go to “on
battery”.
any
Sheds outlets when any UPS device on an upstream line goes to “on
battery”.
recoverdelay
The delay that a UPS device n
eeds to be “on utility” before recovering
outlets. 0-10 minutes.
recovery off
Shed outlets are not recovered Does not recover shed outlets when
even conditions are cleared.
recovery on
Automatically recover shed outlets when event conditions are cleared.
sheddelay
The delay that a UPS device needs to be “on battery” before shedding
outlets. 0-10 minutes.
Usage Guidelines
The Smart Load Shedding feature must be enabled.
Command Access
Admin level only
set location
Sets the system location string.
Command Syntax
set location
Parameters
The set location command uses the following parameter:
location string
Location string text for system location. 0-63 characters.
Command Access
Admin level only