Monitoring > Cords
The Cords page displays cord hardware specifications, overall operational status of each cord, and individual
color-coded graphs and status for cord active power (W), cord apparent power (VA), power factor (if present), and
cord 3-phase out-of-balance level (%).
Note: The inlet type, frequency, power capacity, and energy rating of the cord were determined for the PRO2
product at factory assembly and cannot be user-edited.
What to look for:
The cord power graphs display a blinking warning (yellow) when the total input load exceeds the user-defined
threshold. If an overload occurs, a blinking error condition (red) is displayed. The unit continues to display yellow
and red states until the condition changes or the issue has been resolved.
The default input feed high load threshold is 80% of the input feed maximum load capacity.
Cord power thresholds are user-defined at Configuration > System > Cords.