Server Technology switched pro2 User Manual - page 169
Switched PRO2 – User Guide
Using the Command Line Interface (CLI)
•
169
set phase
Sets phase configuration values.
Command Syntax
set phase email [disabled | enabled]
set phase pf [alarmlo | warnlo]
set phase snmpt [disabled | enabled]
set phase volts [alarmhi | alarmlo | warnhi | warnlo]
set phase volts hyst
For AC products only:
set phase pf hyst
Parameters
The set phase command uses the following parameters:
Sets email notifications for phase events.
hyst
Sets hysteresis between event state and recovery.
pf
Sets power factor. min 0.00, max 1.00, hyst 0.0-0.20 (default 0.02).
snmpt
Sets SNMP trap notifications for phase events.
volts
Sets voltage. min and max vary by product
*
,
hyst 0.0-20
(default 0.02). * For
the min-max range, issue set cord nomvolts all command (press ESC to
quit command).
Sub-Parameters
The set phase command uses the following sub-parameters:
alarmhi
Sets high alarm value.
alarmlo
Sets low alarm value.
warnhi
Sets high warning value.
warnlo
Sets low warning value.
Command Access
Admin level only
set port
Sets serial port configuration values.
Command Syntax
set port [baud | speed] [1200 | 2400 | 4800 | 9600 | 19200 | 38400 | 57600 | 115200]
set port dsrcheck [disabled | enabled]
set port timeout