Server Technology switched pro2 User Manual - page 70
Switched PRO2 – User Guide
Using the Web Interface
•
70
5. View the reported type of socket displayed for the outlet.
6. In the Extra On Delay field, for a specific outlet, set the value (in seconds) for an extra delay when turning
on the outlet. Range is 0-900 seconds.
7. From the drop-down menu, select the On, Off, Last option for the wakeup state of the outlet. Wakeup state
sets the default outlet control state after system power up. The option Last is the last known power state of
the outlet.
8. For the Locked/No Control checkbox, check (to lock the outlet) or uncheck (to unlock the outlet). The
Locked feature determines if control actions (on, off, reboot) are enabled/disabled for the outlet after the
wakeup state is applied. When an outlet is configured in the locked state, the outlet locks at its current
control state (on or off), and the outlet control state changes to Locked On or Locked Off.
Note: The locked outlet will not be affected by group actions or Smart Load Shedding actions. SNMP
and CLI control actions will be ignored for a locked outlet.
9. For each outlet listed, check (or uncheck) SNMP Trap Notifications and/or Email Notifications to enable (or
disable) notifications for outlet events.
10. Click Apply.
Configuring Outlet Current Thresholds
Click the current thresholds link at the bottom of the Outlets page to display the configuration page:
To set outlet current thresholds:
1. Provide threshold hysteresis between event state and recovery (A). Range is 0.0-10.0A; default is 1.0A.
2. Set the low/high alarm and low/high warning threshold values (A) for outlet current load. Range is min 0.0A;
max is max current shown in show outlets command.
3. Click Apply.