– 89 –
CHAPTER 2
Operations of SV8500 Server
STEP 6
Fasten the new FAN with the two screws.
STEP 7
Connect the PWR cables to the connector. This will starts the FAN.
STEP 8
Repeat the steps explained above again for the remaining FANs as needed.
Note:
When replacing two or three FANs while the system is in operation, if you attempt to replace multiple
FANs at a time, the chassis might be heated up. For this reason, when replacing multiple FANs, be sure
to replace them one by one.
7.2 Test Procedure After the Replacement
STEP 1
Check to see if the replaced FANs are operating normally.
•
All FANs are operating normally?
STEP 2
If any FAN is not operating, check the PWR cable of the FAN.
STEP 3
Attach the FAN cover again.
!
・・・・・
・・・・・
・・・・・
・・・
・・・・・
・
MP -48V -48VR
ALM IN (COMMON)
!
・・・・・
・・・・・
・・・・・
・・・
・・・・・
・
MP -48V -48VR
ALM IN (COMMON)
FAN to be replaced