NEC SV8500 Operation And Maintenance Manual - page 632
of
975
– 585 –
CHAPTER 5
Operation Procedure for System with PIR
Note:
Insert the FAN connector firmly to the appropriate FAN connector until you hear an audible click.
STEP 10: Attach the FAN tray again.
•
Insert the FAN tray to the original position.
•
Fix the FAN tray on the FANU again.
STEP 11: Reconnect the cables to the FANU connector, and tighten the screws with a flat-blade screwdriver.
STEP 12: Turn ON (downward) the FAN Power Switch.
•
Check all the FANs are operating normally.
Note:
If FANs do not operate normally, check the cables connections.
STEP 13: Return the FAN cover to the FANU.
STEP 14: Return the front cover of the rack (PIR/TSWR) located just below the FANU.
[END]